Pre-wired protection enclosure for a single-phase charging station up to 7.4 kW: 30 mA type A residual current device and 40 A circuit breaker, in an IP65 waterproof housing.
The Tutélis 40 A type A combines in a single enclosure the two protective devices required at the head of a single-phase charging line. It arrives wired and labelled: the installer only has to connect the incoming supply and the outgoing line to the charging station.
It is suitable for any charging station with its own built-in DC leakage current detection, such as the Ampéa 7.
Box contents
One 40 A, 30 mA, type A double-pole residual current device
One 40 A double-pole circuit breaker, C curve, 6 kA breaking capacity
One earth terminal block and the busbar links
One "Electric vehicle charging" identification label
Two cable glands for cables up to 3 × 10 mm²
Technical specifications
Specification | Value |
Operating voltage | 230 V single-phase |
Rated current | 40 A |
Residual current sensitivity | 30 mA, type A |
Breaking capacity | 6 kA |
Enclosure | 4 modules, transparent door |
Protection rating | IP65 |
Compliance | NF C 15-100, IEC 61008-1 |
Warranty | 2 years |
When to choose a type B
If the charging station does not detect DC leakage currents itself, the standard requires a type B residual current device. In that case, or for a three-phase supply, choose the Tutélis Tétra type B enclosure.
Specifications
Power supply: Single-phase 230 V
Protection rating: IP65
Rating: 40 A
Standard: NF C 15-100
Installation advice
Install the enclosure as close as possible to the main distribution board and locate the "Electric vehicle charging" line on the installation diagram.